EH 61 error code

Indoor pipe temperature sensor T2 sampling voltage is lower than 0.06V or higher than 4.94V.

Severity
technician
Verified
Jul 18, 2026

What triggers it

Indoor pipe temperature sensor T2 sampling voltage is lower than 0.06V or higher than 4.94V.

What to do

  1. Check the connection between the indoor temperature sensor and the indoor PCB.
  2. Correct the wiring if the sensor is not properly connected.
  3. Measure the sensor resistance value against the manual's temperature sensor table.
  4. Replace the sensor if the resistance value is not acceptable.
  5. Replace the indoor main PCB if the sensor resistance is acceptable.

Which systems show it

  • MRCOOL DIY 5th Generation single-zone 9k, 12k, 18k, 24k, and 36k D25 indoor/outdoor models listed in manual section 1.1.

Related codes

Technician scope

T2 sensor, PCB

Source

MRCOOL R454B DIY-5 service manual
Document
data/sources/mrcool-diy5-service.pdf
Section
4.7 TS05-IDU: Indoor temperature sensor error diagnosis and solution
Page
63
Verified Jul 2026