EH 61 error code
Indoor pipe temperature sensor T2 sampling voltage is lower than 0.06V or higher than 4.94V.
- Severity
- technician
- Verified
- Jul 18, 2026
What triggers it
Indoor pipe temperature sensor T2 sampling voltage is lower than 0.06V or higher than 4.94V.
What to do
- Check the connection between the indoor temperature sensor and the indoor PCB.
- Correct the wiring if the sensor is not properly connected.
- Measure the sensor resistance value against the manual's temperature sensor table.
- Replace the sensor if the resistance value is not acceptable.
- Replace the indoor main PCB if the sensor resistance is acceptable.
Which systems show it
- MRCOOL DIY 5th Generation single-zone 9k, 12k, 18k, 24k, and 36k D25 indoor/outdoor models listed in manual section 1.1.
Related codes
Technician scope
T2 sensor, PCB