Friedrich displays an alphanumeric code on the indoor unit, and the 32 codes below cover the Floating Air Pro X, Pro and Select lines, which share a diagnostic scheme. E- codes are generally sensor or communication faults and F- and P- codes are protective shutdowns - the latter usually mean the system stopped itself rather than broke.

Status displays
3
Error codes
32

Unit applicability

Match your unit before reading the table

This table is sourced for Floating Air Pro. If your unit is a different generation or product line not named here, the same display code may vary by generation.

Common codes first

Most broadly applicable documented codes

Ranking basis: we do not have failure-frequency telemetry. These are ordered by breadth of affected systems in the SplitAtlas catalog - the documented product line's published model count, whether the same code appears on more than one product line, and any manual applicability notes we hold. This is a breadth ranking, not a popularity claim.

1

The system is reporting an outdoor coil temperature sensor fault.

AdvisoryTechnician
Breadth evidence
6 published catalog models on its documented product line.
Safe first check
Turn the system off and power cycle once if safe. Do not open panels or replace sensors.
View the fix
2

The compressor exhaust temperature sensor is not reading normally.

AdvisoryTechnician
Breadth evidence
6 published catalog models on its documented product line.
Safe first check
Turn the system off and power cycle once if safe. Do not open the outdoor unit or handle compressor sensors.
View the fix
5

The outdoor inverter power module has entered protection, often with outdoor fan or condenser conditions in the official cause list.

Stop useTechnician
Breadth evidence
6 published catalog models on its documented product line.
Safe first check
Turn the system off. Make sure loose debris, snow, or stored items are not blocking the outdoor unit, but do not reach through grilles or open panels.
View the fix
6

The unit sees supply voltage or internal voltage outside the expected range.

Stop useTechnician
Breadth evidence
6 published catalog models on its documented product line.
Safe first check
Power cycle once only if safe. If code 6 returns, the breaker trips, or home lights flicker, stop and call a technician or electrician.
View the fix
7

The indoor and outdoor units are not exchanging the required control signal.

AdvisoryTechnician
Breadth evidence
6 published catalog models on its documented product line.
Safe first check
Turn the system off and power cycle once if safe. Do not open wiring covers or touch communication wiring.
View the fix
8

The unit has detected an overcurrent condition, with airflow and dirty coil conditions also listed by Friedrich.

Stop useTechnician
Breadth evidence
6 published catalog models on its documented product line.
Safe first check
Turn the system off. Make sure the indoor filter is clean and indoor/outdoor air openings are not blocked. Do not open panels or touch motors.
View the fix

Safe first checks

Checks you can do without opening the unit

These codes have homeowner-safe steps such as filters, airflow, condensate/drain checks, remote/controller items, or a single safe power reset. If the code returns, stop at the boundary in the card.

6Technician

Power cycle once only if safe. If code 6 returns, the breaker trips, or home lights flicker, stop and call a technician or electrician.

Read the full code guide
10Technician

Turn the system off and power cycle once if safe. Do not open the outdoor unit or electrical panels.

Read the full code guide
12DIY

Wait for outdoor conditions to return to the operating range. Do not open the unit. Call for service if code 12 appears when outdoor temperature is not extreme.

Read the full code guide

Friedrich mini-splits

Use the Friedrich catalog to connect these manual error codes to current model pages and replacement options.

Status displays

0

Friedrich lists code 0 as Normal. It is not a failure code.

Not an error
Sourced Jul 2026
Applies to
Floating Air Pro
Homeowner fix
No repair is needed for code 0. If the unit is not operating, continue checking for a separate fault code or normal operating setting.
Status note
This is a status display, not an error code.
View the fix ->

22

Friedrich lists code 22 as the compressor pre heating process and says it is normal mode in cold weather.

Not an error
Sourced Jul 2026
Applies to
Floating Air Pro
Homeowner fix
Wait for the compressor preheat process to finish in cold weather. Service is only needed if the display never clears or heating does not resume.
Status note
This is a status display, not an error code.
View the fix ->

77

Friedrich lists code 77 as Wi-Fi connection enabled with a cycle-power note. It is not a heating or cooling fault by itself.

Not an error
Sourced Jul 2026
Applies to
Floating Air Pro
Homeowner fix
Cycle power from the normal controls as the manual note says if you are completing Wi-Fi setup. No HVAC repair is needed unless the unit will not operate afterward.
Status note
This is a status display, not an error code.
View the fix ->

All error codes

1

The system is reporting an outdoor coil temperature sensor fault.

AdvisoryTechnician
Sourced Jul 2026
Applies to
Floating Air Pro
Homeowner fix
Turn the system off and power cycle once if safe. Do not open panels or replace sensors.
When to call a pro
Call a Friedrich-qualified technician if code 1 returns. Tell them the service manual lists outdoor coil temperature sensor failure.
View the fix ->

10

The outdoor control and drive electronics are not communicating normally.

AdvisoryTechnician
Sourced Jul 2026
Applies to
Floating Air Pro
Homeowner fix
Turn the system off and power cycle once if safe. Do not open the outdoor unit or electrical panels.
When to call a pro
Call a Friedrich-qualified technician if code 10 returns. Tell them the service manual lists communication trouble between outdoor unit and driver.
View the fix ->

11

The outdoor EEPROM memory chip is not seated, installed, or operating normally.

AdvisoryTechnician
Sourced Jul 2026
Applies to
Floating Air Pro
Homeowner fix
Turn the system off and power cycle once if safe. Do not open the outdoor unit or touch control boards.
When to call a pro
Call a Friedrich-qualified technician if code 11 returns. Tell them the service manual lists outdoor EEPROM in trouble.
View the fix ->

12

The outdoor temperature is outside the range where the system will run normally.

AdvisoryDIY
Sourced Jul 2026
Applies to
Floating Air Pro
Homeowner fix
Wait for outdoor conditions to return to the operating range. Do not open the unit. Call for service if code 12 appears when outdoor temperature is not extreme.
When to call a pro
Call a Friedrich-qualified technician if code 12 appears in normal outdoor weather or will not clear. Tell them the manual lists outdoor ambient temperature too low or too high protection.
View the fix ->

13

The compressor discharge/exhaust temperature is too high.

Stop useTechnician
Sourced Jul 2026
Applies to
Floating Air Pro
Homeowner fix
Turn the system off. Do not add refrigerant, open panels, or keep resetting the system.
When to call a pro
Call a Friedrich-qualified technician if code 13 returns. Tell them the service manual lists compressor exhaust temperature too high protection.
View the fix ->

14

The outdoor ambient temperature sensor circuit is not reading normally.

AdvisoryTechnician
Sourced Jul 2026
Applies to
Floating Air Pro
Homeowner fix
Turn the system off and power cycle once if safe. Do not open panels or replace sensors.
When to call a pro
Call a Friedrich-qualified technician if code 14 returns. Tell them the service manual lists outdoor ambient temperature sensor failure.
View the fix ->

15

The compressor shell is too hot or the sensor/refrigerant condition is abnormal.

Stop useTechnician
Sourced Jul 2026
Applies to
Floating Air Pro
Homeowner fix
Turn the system off. Do not add refrigerant, open panels, or keep resetting the system.
When to call a pro
Call a Friedrich-qualified technician if code 15 returns. Tell them the service manual lists compressor shell temperature too high protection.
View the fix ->

16

The indoor coil is too cold in cooling or overloaded in heating, and the manual lists sensor, board, and refrigerant-system causes.

AdvisoryTechnician
Sourced Jul 2026
Applies to
Floating Air Pro
Homeowner fix
Turn the system off. Make sure the filter is clean and indoor airflow is not blocked. Do not open panels or handle refrigerant parts.
When to call a pro
Call a Friedrich-qualified technician if code 16 returns. Tell them the service manual lists anti-freeze or overload protection.
View the fix ->

17

The power factor correction circuit or outdoor drive board has entered protection.

Stop useTechnician
Sourced Jul 2026
Applies to
Floating Air Pro
Homeowner fix
Turn the system off and power cycle once if safe. Do not open electrical panels or keep resetting the system.
When to call a pro
Call a Friedrich-qualified technician if code 17 returns. Tell them the service manual lists PFC protection.
View the fix ->

18

The DC inverter compressor did not start normally.

Stop useTechnician
Sourced Jul 2026
Applies to
Floating Air Pro
Homeowner fix
Turn the system off and power cycle once if safe. Do not open the outdoor unit or attempt compressor work.
When to call a pro
Call a Friedrich-qualified technician if code 18 returns. Tell them the service manual lists DC compressor start failure.
View the fix ->

19

The compressor drive system has failed or is not operating normally.

Stop useTechnician
Sourced Jul 2026
Applies to
Floating Air Pro
Homeowner fix
Turn the system off and power cycle once if safe. Do not open the outdoor unit or attempt compressor/inverter work.
When to call a pro
Call a Friedrich-qualified technician if code 19 returns. Tell them the service manual lists compressor drive failure.
View the fix ->

2

The compressor exhaust temperature sensor is not reading normally.

AdvisoryTechnician
Sourced Jul 2026
Applies to
Floating Air Pro
Homeowner fix
Turn the system off and power cycle once if safe. Do not open the outdoor unit or handle compressor sensors.
When to call a pro
Call a Friedrich-qualified technician if code 2 returns. Tell them the service manual lists compressor exhaust temperature sensor trouble.
View the fix ->

20

The outdoor fan is locked, blocked, disconnected, failed, or controlled abnormally.

AdvisoryTechnician
Sourced Jul 2026
Applies to
Floating Air Pro
Homeowner fix
Turn the system off. Remove only loose debris outside the cabinet if safe. Do not reach through grilles, spin the fan by hand, or open panels.
When to call a pro
Call a Friedrich-qualified technician if code 20 returns. Tell them the service manual lists outdoor fan motor locked rotor protection.
View the fix ->

21

The outdoor coil is in anti-overload protection while cooling.

AdvisoryTechnician
Sourced Jul 2026
Applies to
Floating Air Pro
Homeowner fix
Turn the system off. Make sure indoor and outdoor air openings are not blocked. Do not open panels, clean coils with tools, or handle refrigerant.
When to call a pro
Call a Friedrich-qualified technician if code 21 returns. Tell them the service manual lists outdoor coil anti-overload protection with cooling.
View the fix ->

23

Friedrich lists code 23 as a product leak involving the indoor unit, outdoor unit, or connecting pipe.

Stop useTechnician
Sourced Jul 2026
Applies to
Floating Air Pro
Homeowner fix
Stop using the system, avoid ignition sources near the indoor unit, ventilate if safe, and call for service. Do not clear the code or add refrigerant.
When to call a pro
Call a Friedrich-qualified technician immediately. Tell them the service manual lists code 23 as a product leak.
View the fix ->

24

The outdoor board/chip fault is tied by Friedrich to mismatched drive-board or compressor usage.

AdvisoryTechnician
Sourced Jul 2026
Applies to
Floating Air Pro
Homeowner fix
Turn the system off and do not open the outdoor unit or change parts. If this appeared after repair, call the installer.
When to call a pro
Call a Friedrich-qualified technician if code 24 appears. Tell them the service manual lists outdoor board chip failure.
View the fix ->

26

The outdoor radiator/heat-sink area is overheating or its sensing circuit is abnormal.

AdvisoryTechnician
Sourced Jul 2026
Applies to
Floating Air Pro
Homeowner fix
Turn the system off. Make sure the outdoor unit is not covered or blocked, but do not open the cabinet or electrical panels.
When to call a pro
Call a Friedrich-qualified technician if code 26 returns. Tell them the service manual lists overheated outdoor radiator.
View the fix ->

27

The system has detected or is reporting excessive pressure protection.

Stop useTechnician
Sourced Jul 2026
Applies to
Floating Air Pro
Homeowner fix
Turn the system off. Check only that the outdoor unit is not blocked; do not open panels or touch refrigerant parts.
When to call a pro
Call a Friedrich-qualified technician if code 27 appears. Tell them the service manual lists protection against too high system pressure.
View the fix ->

33

The indoor room temperature sensor circuit is not reading normally.

AdvisoryTechnician
Sourced Jul 2026
Applies to
Floating Air Pro
Homeowner fix
Turn the system off and power cycle once if safe. Do not open the indoor unit or replace sensors.
When to call a pro
Call a Friedrich-qualified technician if code 33 returns. Tell them the service manual lists indoor room temperature sensor failure.
View the fix ->

34

The indoor coil temperature sensor circuit is not reading normally.

AdvisoryTechnician
Sourced Jul 2026
Applies to
Floating Air Pro
Homeowner fix
Turn the system off and power cycle once if safe. Do not open the indoor unit or replace sensors.
When to call a pro
Call a Friedrich-qualified technician if code 34 returns. Tell them the service manual lists indoor coil temperature sensor failure.
View the fix ->

36

The indoor and outdoor units are not exchanging the required control signal.

AdvisoryTechnician
Sourced Jul 2026
Applies to
Floating Air Pro
Homeowner fix
Turn the system off and power cycle once if safe. Do not open wiring covers or touch communication wiring.
When to call a pro
Call a Friedrich-qualified technician if code 36 returns. Tell them the service manual lists indoor/outdoor communication failure.
View the fix ->

38

The indoor EEPROM memory chip or indoor control board is not operating normally.

AdvisoryTechnician
Sourced Jul 2026
Applies to
Floating Air Pro
Homeowner fix
Turn the system off and power cycle once if safe. Do not open the indoor unit or touch control boards.
When to call a pro
Call a Friedrich-qualified technician if code 38 returns. Tell them the service manual lists indoor EEPROM failure.
View the fix ->

39

The indoor fan motor is blocked, disconnected, failed, or controlled abnormally.

AdvisoryTechnician
Sourced Jul 2026
Applies to
Floating Air Pro
Homeowner fix
Turn the system off and make sure furniture or loose items are not blocking the indoor unit. Do not reach into the fan or open the cabinet.
When to call a pro
Call a Friedrich-qualified technician if code 39 returns. Tell them the service manual lists indoor fan motor running abnormally.
View the fix ->

41

The indoor unit has a grounding protection fault that Friedrich ties to the indoor control board.

Stop useTechnician
Sourced Jul 2026
Applies to
Floating Air Pro
Homeowner fix
Turn the system off. Do not open electrical panels or keep resetting the system.
When to call a pro
Call a Friedrich-qualified technician if code 41 appears. Tell them the service manual lists indoor grounding protection failure.
View the fix ->

5

The outdoor inverter power module has entered protection, often with outdoor fan or condenser conditions in the official cause list.

Stop useTechnician
Sourced Jul 2026
Applies to
Floating Air Pro
Homeowner fix
Turn the system off. Make sure loose debris, snow, or stored items are not blocking the outdoor unit, but do not reach through grilles or open panels.
When to call a pro
Call a Friedrich-qualified technician if code 5 returns. Tell them the service manual lists IPM module protection.
View the fix ->

56

Friedrich lists code 56 as a product leak and notes the indoor fan is forced to high speed while the outdoor unit stops.

Stop useTechnician
Sourced Jul 2026
Applies to
Floating Air Pro
Homeowner fix
Stop using the system, avoid ignition sources near the indoor unit, ventilate if safe, and call for service. Do not clear the code or add refrigerant.
When to call a pro
Call a Friedrich-qualified technician immediately. Tell them the service manual lists code 56 as a refrigerant leakage fault that requires repair before clearing.
View the fix ->

57

The refrigerant sensor and indoor control board are not communicating normally.

AdvisoryTechnician
Sourced Jul 2026
Applies to
Floating Air Pro
Homeowner fix
Turn the system off and power cycle once if safe. Do not open the indoor unit, bypass the refrigerant sensor, or touch wiring.
When to call a pro
Call a Friedrich-qualified technician if code 57 returns. Tell them the service manual lists refrigerant-sensor/control-board communication trouble.
View the fix ->

6

The unit sees supply voltage or internal voltage outside the expected range.

Stop useTechnician
Sourced Jul 2026
Applies to
Floating Air Pro
Homeowner fix
Power cycle once only if safe. If code 6 returns, the breaker trips, or home lights flicker, stop and call a technician or electrician.
When to call a pro
Call a Friedrich-qualified technician if code 6 returns. Tell them the service manual lists AC voltage higher or lower protection.
View the fix ->

7

The indoor and outdoor units are not exchanging the required control signal.

AdvisoryTechnician
Sourced Jul 2026
Applies to
Floating Air Pro
Homeowner fix
Turn the system off and power cycle once if safe. Do not open wiring covers or touch communication wiring.
When to call a pro
Call a Friedrich-qualified technician if code 7 returns. Tell them the service manual lists indoor/outdoor communication failure.
View the fix ->

8

The unit has detected an overcurrent condition, with airflow and dirty coil conditions also listed by Friedrich.

Stop useTechnician
Sourced Jul 2026
Applies to
Floating Air Pro
Homeowner fix
Turn the system off. Make sure the indoor filter is clean and indoor/outdoor air openings are not blocked. Do not open panels or touch motors.
When to call a pro
Call a Friedrich-qualified technician if code 8 returns. Tell them the service manual lists current overload protection.
View the fix ->

9

The unit has detected a high current protection condition tied to short-circuit causes in the manual.

Stop useTechnician
Sourced Jul 2026
Applies to
Floating Air Pro
Homeowner fix
Turn the system off. Do not keep resetting it, and do not open electrical panels.
When to call a pro
Call a Friedrich-qualified technician if code 9 appears. Tell them the service manual lists maximum current protection.
View the fix ->

EA

The indoor display and indoor control board are not communicating normally.

AdvisoryTechnician
Sourced Jul 2026
Applies to
Floating Air Pro
Homeowner fix
Turn the system off and power cycle once if safe. Do not open the indoor unit or touch wiring.
When to call a pro
Call a Friedrich-qualified technician if EA returns. Tell them the service manual lists EA as interrupted display-board/control-board communication.
View the fix ->