EC 54 error code

Compressor discharge temperature sensor TP sampling voltage is lower than 0.06V or higher than 4.94V.

Severity
technician
Verified
Jul 18, 2026

What triggers it

Compressor discharge temperature sensor TP sampling voltage is lower than 0.06V or higher than 4.94V.

What to do

  1. Check the connection between the outdoor temperature sensor and the outdoor PCB.
  2. Correct the wiring if the sensor is not properly connected.
  3. Measure the sensor resistance value against the manual's temperature sensor table.
  4. Replace the sensor if the resistance value is not acceptable.
  5. Replace the outdoor main PCB if the sensor resistance is acceptable.

Which systems show it

  • MRCOOL DIY 5th Generation single-zone 9k, 12k, 18k, 24k, and 36k D25 indoor/outdoor models listed in manual section 1.1.
  • For certain models the outdoor unit uses a combination sensor where T3, T4, and TP are the same sensor.

Related codes

Technician scope

Sensors, outdoor PCB

Source

MRCOOL R454B DIY-5 service manual