SplitAtlas

MRCOOL / DIY 5th Generation

PC 00 error code

The voltage signal sent from the IPM to the compressor drive chip is abnormal.

Severity
technician
Verified
Jul 18, 2026

What triggers it

The voltage signal sent from the IPM to the compressor drive chip is abnormal.

What to do

  1. Check wiring between the outdoor PCB and compressor; correct or replace wires and connectors if faulty.
  2. Check IPM installation; tighten screws and apply silicon grease if installation is not correct.
  3. Perform the manual's IPM continuity check; replace the IPM board or outdoor PCB when terminal resistance is not uniform.
  4. Check outdoor fan operation and outdoor ventilation; use the fan-speed troubleshooting procedure if needed.
  5. Measure compressor resistance; replace the compressor if resistance is not uniform, otherwise replace the outdoor PCB.

Which systems show it

  • MRCOOL DIY 5th Generation single-zone 9k, 12k, 18k, 24k, and 36k D25 indoor/outdoor models listed in manual section 1.1.

Related codes

Technician scope

IPM board, compressor, outdoor PCB

Source

MRCOOL R454B DIY-5 service manual
Document
data/sources/mrcool-diy5-service.pdf
Section
4.7 TS09-S: IPM module protection diagnosis and solution
Page
70
Verified Jul 2026

Next step