Toshiba Carrier error codes

Toshiba Carrier is the Toshiba and Carrier joint venture, and its systems use Toshiba's diagnostic scheme: a letter-plus-number code on the indoor unit or wired controller, with a check-code readout available through the remote. The 49 codes below come from Toshiba Carrier's own service literature and will look different from Carrier's own ductless range, which has separate pages here.

Status displays
0
Error codes
49

Unit applicability

Match your unit before reading the table

This table is sourced for Toshiba Carrier 26 High Wall. If your unit is a different generation or product line not named here, the same display code may vary by generation.

Common codes first

Most broadly applicable documented codes

Ranking basis: we do not have failure-frequency telemetry. These are ordered by breadth of affected systems in the SplitAtlas catalog - the documented product line's published model count, whether the same code appears on more than one product line, and any manual applicability notes we hold. This is a breadth ranking, not a popularity claim.

E01

The Toshiba Carrier troubleshooting table lists E01 as no header remote controller. It points to incorrect remote controller setting, a header remote controller not being set, or no signal being received from the indoor unit.

AdvisoryTechnician
Breadth evidence
5 published catalog models on its documented product line.
Safe first check
Power cycle the system once if you can do that safely. Do not open the indoor unit or change wired-controller address settings.
View the fix
E02

The Toshiba Carrier table lists E02 as a remote controller transmission error. It says no signal can be sent to the indoor unit and lists system interconnection wires, the indoor PCB, and the remote controller as parts to check.

AdvisoryTechnician
Breadth evidence
5 published catalog models on its documented product line.
Safe first check
Power cycle the system once if you can do that safely. Do not open wiring covers or move controller wiring.
View the fix
E03

The Toshiba Carrier table lists E03 as an indoor unit to remote controller regular communication error. It says data is not being received from the remote controller or network adapter.

AdvisoryTechnician
Breadth evidence
5 published catalog models on its documented product line.
Safe first check
Power cycle the system once if you can do that safely. Do not open the unit or change controller/network adapter wiring.
View the fix
E04

The Toshiba Carrier table lists E04 as an indoor unit to outdoor unit serial communication error. It points to the system interconnection wires, indoor PCB, and outdoor PCB.

AdvisoryTechnician
Breadth evidence
5 published catalog models on its documented product line.
Safe first check
Power cycle the system once at the breaker if you can do that safely. Do not open indoor or outdoor wiring covers.
View the fix
E08

The Toshiba Carrier table lists E08 as duplicated indoor addresses. It says the indoor address setting is wrong because the same address as the unit's own address was detected.

AdvisoryTechnician
Breadth evidence
5 published catalog models on its documented product line.
Safe first check
Power cycle the system once if you can do that safely. Do not change address settings in the controller or on the unit.
View the fix
E09

The Toshiba Carrier table lists E09 as duplicated header remote controllers. It says two remote controllers are set as header in double-remote control.

AdvisoryTechnician
Breadth evidence
5 published catalog models on its documented product line.
Safe first check
Power cycle once if you can do that safely. Do not change hidden controller address or header/follower settings.
View the fix

Safe first checks

Checks you can do without opening the unit

These codes have homeowner-safe steps such as filters, airflow, condensate/drain checks, remote/controller items, or a single safe power reset. If the code returns, stop at the boundary in the card.

E08Technician

Power cycle the system once if you can do that safely. Do not change address settings in the controller or on the unit.

Read the full code guide
E09Technician

Power cycle once if you can do that safely. Do not change hidden controller address or header/follower settings.

Read the full code guide
E31Technician

Turn the system off and power cycle once only if you can do that safely. Do not open the outdoor unit.

Read the full code guide

Toshiba Carrier mini-splits

Use the Toshiba Carrier catalog to connect these manual error codes to current model pages and replacement options.

All error codes

E01

The Toshiba Carrier troubleshooting table lists E01 as no header remote controller. It points to incorrect remote controller setting, a header remote controller not being set, or no signal being received from the indoor unit.

AdvisoryTechnician
Sourced Jul 2026
Applies to
Toshiba Carrier 26 High Wall
Homeowner fix
Power cycle the system once if you can do that safely. Do not open the indoor unit or change wired-controller address settings.
When to call a pro
Call a licensed HVAC technician if E01 returns. Tell them Toshiba Carrier lists E01 as no header remote controller or incorrect header controller setup.
View the fix ->

E02

The Toshiba Carrier table lists E02 as a remote controller transmission error. It says no signal can be sent to the indoor unit and lists system interconnection wires, the indoor PCB, and the remote controller as parts to check.

AdvisoryTechnician
Sourced Jul 2026
Applies to
Toshiba Carrier 26 High Wall
Homeowner fix
Power cycle the system once if you can do that safely. Do not open wiring covers or move controller wiring.
When to call a pro
Call a licensed HVAC technician if E02 returns. Tell them Toshiba Carrier identifies E02 as a remote controller transmission error.
View the fix ->

E03

The Toshiba Carrier table lists E03 as an indoor unit to remote controller regular communication error. It says data is not being received from the remote controller or network adapter.

AdvisoryTechnician
Sourced Jul 2026
Applies to
Toshiba Carrier 26 High Wall
Homeowner fix
Power cycle the system once if you can do that safely. Do not open the unit or change controller/network adapter wiring.
When to call a pro
Call a licensed HVAC technician if E03 returns. Tell them Toshiba Carrier lists E03 as an indoor-to-controller regular communication error.
View the fix ->

E04

The Toshiba Carrier table lists E04 as an indoor unit to outdoor unit serial communication error. It points to the system interconnection wires, indoor PCB, and outdoor PCB.

AdvisoryTechnician
Sourced Jul 2026
Applies to
Toshiba Carrier 26 High Wall
Homeowner fix
Power cycle the system once at the breaker if you can do that safely. Do not open indoor or outdoor wiring covers.
When to call a pro
Call a licensed HVAC technician if E04 returns or appeared after installation. Tell them Toshiba Carrier maps E04 to indoor/outdoor serial communication.
View the fix ->

E08

The Toshiba Carrier table lists E08 as duplicated indoor addresses. It says the indoor address setting is wrong because the same address as the unit's own address was detected.

AdvisoryTechnician
Sourced Jul 2026
Applies to
Toshiba Carrier 26 High Wall
Homeowner fix
Power cycle the system once if you can do that safely. Do not change address settings in the controller or on the unit.
When to call a pro
Call a licensed HVAC technician if E08 returns. Tell them Toshiba Carrier identifies E08 as duplicated indoor addresses.
View the fix ->

E09

The Toshiba Carrier table lists E09 as duplicated header remote controllers. It says two remote controllers are set as header in double-remote control.

AdvisoryTechnician
Sourced Jul 2026
Applies to
Toshiba Carrier 26 High Wall
Homeowner fix
Power cycle once if you can do that safely. Do not change hidden controller address or header/follower settings.
When to call a pro
Call a licensed HVAC technician if E09 returns. Tell them Toshiba Carrier lists E09 as duplicated header remote controllers.
View the fix ->

E10

The Toshiba Carrier table lists E10 as CPU-CPU communication error. It points to the indoor PCB and says communication between the main MCU and motor microcomputer MCU is abnormal.

AdvisoryTechnician
Sourced Jul 2026
Applies to
Toshiba Carrier 26 High Wall
Homeowner fix
Power cycle once if you can do that safely. Do not open the indoor cabinet or touch the control board.
When to call a pro
Call a licensed HVAC technician if E10 returns. Tell them Toshiba Carrier identifies E10 as indoor PCB CPU-to-CPU communication trouble.
View the fix ->

E18

The Toshiba Carrier table lists E18 as header unit to follower unit regular communication error. It says communication is impossible between header and follower indoor units, including twin header/follower units.

AdvisoryTechnician
Sourced Jul 2026
Applies to
Toshiba Carrier 26 High Wall
Homeowner fix
Power cycle once if you can do that safely. Do not change group or header/follower settings.
When to call a pro
Call a licensed HVAC technician if E18 returns. Tell them Toshiba Carrier identifies E18 as header/follower indoor-unit communication trouble.
View the fix ->

E31

The Toshiba Carrier table lists E31 as IPDU communication error. It says communication between the IPDU and CDB is abnormal and points to the outdoor unit.

Stop useTechnician
Sourced Jul 2026
Applies to
Toshiba Carrier 26 High Wall
Homeowner fix
Turn the system off and power cycle once only if you can do that safely. Do not open the outdoor unit.
When to call a pro
Call a licensed HVAC technician if E31 returns. Tell them Toshiba Carrier identifies E31 as outdoor IPDU communication error.
View the fix ->

F01

The Toshiba Carrier table lists F01 as indoor heat exchanger sensor TCJ error. It says an open or short circuit has been detected and lists the TCJ heat exchanger sensor and indoor PCB as parts to check.

AdvisoryTechnician
Sourced Jul 2026
Applies to
Toshiba Carrier 26 High Wall
Homeowner fix
Power cycle once if you can do that safely. Keep the indoor unit's air path clear, but do not open the cabinet.
When to call a pro
Call a licensed HVAC technician if F01 returns. Tell them Toshiba Carrier identifies F01 as indoor heat exchanger TCJ sensor error.
View the fix ->

F02

The Toshiba Carrier table lists F02 as indoor heat exchanger sensor TC error. It says an open or short circuit has been detected and lists the TC heat exchanger sensor and indoor PCB as parts to check.

AdvisoryTechnician
Sourced Jul 2026
Applies to
Toshiba Carrier 26 High Wall
Homeowner fix
Power cycle once if you can do that safely. Keep the indoor unit's air path clear, but do not open the cabinet.
When to call a pro
Call a licensed HVAC technician if F02 returns. Tell them Toshiba Carrier identifies F02 as indoor heat exchanger TC sensor error.
View the fix ->

F04

The Toshiba Carrier table lists F04 as outdoor discharge temperature sensor TD error. It says an open or short circuit has been detected and lists the outdoor TD temperature sensor and outdoor PCB as parts to check.

Stop useTechnician
Sourced Jul 2026
Applies to
Toshiba Carrier 26 High Wall
Homeowner fix
Power cycle once only if you can do that safely. Do not open the outdoor unit or handle refrigerant-line sensors.
When to call a pro
Call a licensed HVAC technician if F04 returns. Tell them Toshiba Carrier identifies F04 as outdoor discharge temperature TD sensor error.
View the fix ->

F06

The Toshiba Carrier table lists F06 as outdoor temperature sensor TE/TS error. It says an open or short circuit of a heat exchanger temperature sensor has been detected and lists outdoor temperature sensors TE/TS and the outdoor PCB.

Stop useTechnician
Sourced Jul 2026
Applies to
Toshiba Carrier 26 High Wall
Homeowner fix
Power cycle once only if you can do that safely. Keep the outdoor cabinet clear of debris, but do not open it.
When to call a pro
Call a licensed HVAC technician if F06 returns. Tell them Toshiba Carrier identifies F06 as outdoor TE/TS temperature sensor error.
View the fix ->

F07

The Toshiba Carrier table lists F07 as TL sensor error. It says the TL sensor may be displaced, disconnected, or short-circuited.

Stop useTechnician
Sourced Jul 2026
Applies to
Toshiba Carrier 26 High Wall
Homeowner fix
Power cycle once only if you can do that safely. Do not open the outdoor unit or reposition sensors.
When to call a pro
Call a licensed HVAC technician if F07 returns. Tell them Toshiba Carrier identifies F07 as TL sensor displaced, disconnected, or short-circuited.
View the fix ->

F08

The Toshiba Carrier table lists F08 as outdoor outside air temperature sensor error. It says an open or short circuit has been detected and lists the TO outdoor temperature sensor and outdoor PCB as parts to check.

AdvisoryTechnician
Sourced Jul 2026
Applies to
Toshiba Carrier 26 High Wall
Homeowner fix
Power cycle once if you can do that safely. Make sure the outdoor unit is not buried in debris, but do not open the cabinet.
When to call a pro
Call a licensed HVAC technician if F08 returns. Tell them Toshiba Carrier identifies F08 as outdoor outside-air TO sensor error.
View the fix ->

F10

The Toshiba Carrier table lists F10 as indoor room temperature sensor TA error. It says an open or short circuit has been detected and lists the TA room temperature sensor and indoor PCB as parts to check.

AdvisoryTechnician
Sourced Jul 2026
Applies to
Toshiba Carrier 26 High Wall
Homeowner fix
Power cycle once if you can do that safely. Keep the indoor unit clear of heat sources and blocked airflow, but do not open the cabinet.
When to call a pro
Call a licensed HVAC technician if F10 returns. Tell them Toshiba Carrier identifies F10 as indoor room-temperature TA sensor error.
View the fix ->

F12

The Toshiba Carrier table lists F12 as TS sensor error. It says the TS sensor may be displaced, disconnected, or short-circuited.

Stop useTechnician
Sourced Jul 2026
Applies to
Toshiba Carrier 26 High Wall
Homeowner fix
Power cycle once only if you can do that safely. Do not open the outdoor unit or reposition sensors.
When to call a pro
Call a licensed HVAC technician if F12 returns. Tell them Toshiba Carrier identifies F12 as TS sensor displaced, disconnected, or short-circuited.
View the fix ->

F13

The Toshiba Carrier table lists F13 as heat sink sensor error. It says abnormal temperature was detected by the IGBT heat-sink temperature sensor.

Stop useTechnician
Sourced Jul 2026
Applies to
Toshiba Carrier 26 High Wall
Homeowner fix
Turn the system off if F13 returns. Keep the outdoor unit clear of leaves and debris outside the cabinet, but do not open it.
When to call a pro
Call a licensed HVAC technician if F13 returns. Tell them Toshiba Carrier identifies F13 as IGBT heat-sink sensor abnormal temperature.
View the fix ->

F15

The Toshiba Carrier table lists F15 as temperature sensor connection error. It says the TE and TS sensors may be connected incorrectly.

Stop useTechnician
Sourced Jul 2026
Applies to
Toshiba Carrier 26 High Wall
Homeowner fix
Turn the system off if F15 returns. Do not open the outdoor unit or move sensor plugs.
When to call a pro
Call a licensed HVAC technician if F15 returns. Tell them Toshiba Carrier identifies F15 as TE/TS temperature sensor connection error.
View the fix ->

F29

The Toshiba Carrier table lists F29 as indoor unit other PCB error and identifies it as an indoor PCB EEPROM error.

AdvisoryTechnician
Sourced Jul 2026
Applies to
Toshiba Carrier 26 High Wall
Homeowner fix
Power cycle once if you can do that safely. Do not open the indoor unit or touch the control board.
When to call a pro
Call a licensed HVAC technician if F29 returns. Tell them Toshiba Carrier identifies F29 as indoor PCB EEPROM error.
View the fix ->

F31

The Toshiba Carrier table lists F31 as outdoor unit PCB error and identifies it as an outdoor PCB EEPROM error.

Stop useTechnician
Sourced Jul 2026
Applies to
Toshiba Carrier 26 High Wall
Homeowner fix
Power cycle once only if you can do that safely. Do not open the outdoor unit or touch electronics.
When to call a pro
Call a licensed HVAC technician if F31 returns. Tell them Toshiba Carrier identifies F31 as outdoor PCB EEPROM error.
View the fix ->

H01

The Toshiba Carrier table lists H01 as outdoor compressor breakdown. It points to the current-detect circuit and power voltage, including current releasing control at minimum frequency or short-circuit current after direct excitation.

Stop useTechnician
Sourced Jul 2026
Applies to
Toshiba Carrier 26 High Wall
Homeowner fix
Turn the system off. Do not keep resetting it and do not open the outdoor unit.
When to call a pro
Call a licensed HVAC technician for H01. Tell them Toshiba Carrier identifies H01 as outdoor compressor breakdown with current-detect and power-voltage checks.
View the fix ->

H02

The Toshiba Carrier table lists H02 as outdoor compressor lock. It points to the compressor circuit and says compressor lock was detected.

Stop useTechnician
Sourced Jul 2026
Applies to
Toshiba Carrier 26 High Wall
Homeowner fix
Turn the system off. Do not keep resetting it and do not open the outdoor unit.
When to call a pro
Call a licensed HVAC technician for H02. Tell them Toshiba Carrier identifies H02 as outdoor compressor lock.
View the fix ->

H03

The Toshiba Carrier table lists H03 as outdoor current detect circuit error. It points to the current-detect circuit and outdoor PCB and describes abnormal current in AC-CT or phase loss.

Stop useTechnician
Sourced Jul 2026
Applies to
Toshiba Carrier 26 High Wall
Homeowner fix
Turn the system off. Do not reset repeatedly or open the outdoor electrical compartment.
When to call a pro
Call a licensed HVAC technician for H03. Tell them Toshiba Carrier identifies H03 as current-detect circuit error or phase-loss related abnormal current.
View the fix ->

H04

The Toshiba Carrier table lists H04 as case thermostat operation and describes it as a malfunction of the case thermostat.

Stop useTechnician
Sourced Jul 2026
Applies to
Toshiba Carrier 26 High Wall
Homeowner fix
Turn the system off if H04 returns. Do not open the outdoor unit or bypass protective devices.
When to call a pro
Call a licensed HVAC technician if H04 returns. Tell them Toshiba Carrier identifies H04 as case thermostat operation.
View the fix ->

H06

The Toshiba Carrier table lists H06 as outdoor low-pressure system error. It points to current, the high-pressure switch circuit, and outdoor PCB, and says a pressure sensor error or low-pressure protective operation was activated.

Stop useTechnician
Sourced Jul 2026
Applies to
Toshiba Carrier 26 High Wall
Homeowner fix
Turn the system off. Do not keep resetting it or connect gauges.
When to call a pro
Call a licensed HVAC technician for H06. Tell them Toshiba Carrier identifies H06 as low-pressure system error or pressure-sensor/protection operation.
View the fix ->

L03

The Toshiba Carrier table lists L03 as duplicated header indoor units. It says two or more header units are set in the same group.

AdvisoryTechnician
Sourced Jul 2026
Applies to
Toshiba Carrier 26 High Wall
Homeowner fix
Power cycle once if you can do that safely. Do not change group or address settings.
When to call a pro
Call a licensed HVAC technician if L03 returns. Tell them Toshiba Carrier identifies L03 as duplicated header indoor units.
View the fix ->

L07

The Toshiba Carrier table lists L07 as group line in individual indoor unit. It says at least one group-connected indoor unit exists among individual indoor units.

AdvisoryTechnician
Sourced Jul 2026
Applies to
Toshiba Carrier 26 High Wall
Homeowner fix
Power cycle once if you can do that safely. Do not change group settings or controller wiring.
When to call a pro
Call a licensed HVAC technician if L07 returns. Tell them Toshiba Carrier identifies L07 as group line in an individual indoor unit.
View the fix ->

L08

The Toshiba Carrier table lists L08 as indoor group address not set. It says the indoor address group is not set.

AdvisoryTechnician
Sourced Jul 2026
Applies to
Toshiba Carrier 26 High Wall
Homeowner fix
Power cycle once if you can do that safely. Do not change controller address settings.
When to call a pro
Call a licensed HVAC technician if L08 returns. Tell them Toshiba Carrier identifies L08 as indoor group address not set.
View the fix ->

L09

The Toshiba Carrier table lists L09 as indoor unit capacity not set. It says the unit capacity has not been set.

AdvisoryTechnician
Sourced Jul 2026
Applies to
Toshiba Carrier 26 High Wall
Homeowner fix
Power cycle once if you can do that safely. Do not change capacity settings or control-board switches.
When to call a pro
Call a licensed HVAC technician if L09 returns. Tell them Toshiba Carrier identifies L09 as indoor unit capacity not set.
View the fix ->

L10

The Toshiba Carrier table lists L10 under outdoor unit PCB and identifies it as an outdoor PCB jumper wire, for service, setting error.

Stop useTechnician
Sourced Jul 2026
Applies to
Toshiba Carrier 26 High Wall
Homeowner fix
Turn the system off if L10 returns. Do not open the outdoor unit or move jumpers.
When to call a pro
Call a licensed HVAC technician if L10 returns. Tell them Toshiba Carrier identifies L10 as an outdoor PCB service jumper setting error.
View the fix ->

L20

The Toshiba Carrier table lists L20 as LAN communication error. It points to address setting, central control remote, and network adapter, and says an address is duplicated in central control communication.

AdvisoryTechnician
Sourced Jul 2026
Applies to
Toshiba Carrier 26 High Wall
Homeowner fix
Power cycle once if you can do that safely. Do not change network adapter or central-control address settings.
When to call a pro
Call a licensed HVAC technician if L20 returns. Tell them Toshiba Carrier identifies L20 as LAN communication error with duplicated central-control address.
View the fix ->

L29

The Toshiba Carrier table lists L29 as other outdoor unit error. It includes communication error between the IPDU MCU and CDB MCU and abnormal temperature detected by the IGBT heat-sink temperature sensor.

Stop useTechnician
Sourced Jul 2026
Applies to
Toshiba Carrier 26 High Wall
Homeowner fix
Turn the system off if L29 returns. Keep the outdoor unit clear outside the cabinet, but do not open it.
When to call a pro
Call a licensed HVAC technician for L29. Tell them Toshiba Carrier lists outdoor MCU communication and IGBT heat-sink temperature conditions under this code.
View the fix ->

L30

The Toshiba Carrier table lists L30 as abnormal external input into indoor unit, interlock. It points to external devices and outdoor PCB, and says there is an abnormal stop due to incorrect external input into CN80.

AdvisoryTechnician
Sourced Jul 2026
Applies to
Toshiba Carrier 26 High Wall
Homeowner fix
Power cycle once if you can do that safely. Do not bypass external safety or interlock devices.
When to call a pro
Call a licensed HVAC technician if L30 returns. Tell them Toshiba Carrier identifies L30 as abnormal external interlock input into CN80.
View the fix ->

L31

The Toshiba Carrier table lists L31 as phase sequence error and says abnormal phase sequence of three-phase power was detected. It points to the power supply phase sequence and outdoor PCB.

Stop useTechnician
Sourced Jul 2026
Applies to
Toshiba Carrier 26 High Wall
Homeowner fix
Turn the system off. Do not reset repeatedly or open electrical panels.
When to call a pro
Call a licensed HVAC technician or qualified electrician for L31. Tell them Toshiba Carrier identifies it as phase-sequence error or three-phase power abnormality.
View the fix ->

P01

The Toshiba Carrier table lists P01 as indoor fan error. It points to the indoor fan motor and indoor PCB and says the indoor AC fan error occurs when the fan motor thermal relay is activated.

AdvisoryTechnician
Sourced Jul 2026
Applies to
Toshiba Carrier 26 High Wall
Homeowner fix
Turn the unit off if the indoor fan is not moving, is noisy, or smells hot. You can check from outside that the inlet and outlet are not blocked.
When to call a pro
Call a licensed HVAC technician if P01 returns. Tell them Toshiba Carrier identifies P01 as indoor fan error or fan motor thermal relay activation.
View the fix ->

P03

The Toshiba Carrier table lists P03 as outdoor discharge temperature error and describes it as an error in discharge-temperature releasing control.

Stop useTechnician
Sourced Jul 2026
Applies to
Toshiba Carrier 26 High Wall
Homeowner fix
Turn the system off if P03 returns. Do not keep resetting it or open the outdoor unit.
When to call a pro
Call a licensed HVAC technician for P03. Tell them Toshiba Carrier identifies it as outdoor discharge-temperature releasing-control error.
View the fix ->

P04

The Toshiba Carrier table lists P04 as outdoor high-pressure system error. It points to the high-pressure switch and says IOL activated or high-pressure releasing control using TE is in error.

Stop useTechnician
Sourced Jul 2026
Applies to
Toshiba Carrier 26 High Wall
Homeowner fix
Turn the system off. Make sure the outdoor unit is not blocked by leaves or objects outside the cabinet, but do not open it or connect gauges.
When to call a pro
Call a licensed HVAC technician for P04. Tell them Toshiba Carrier identifies P04 as outdoor high-pressure system error.
View the fix ->

P05

The Toshiba Carrier table lists P05 as open phase detected. It says the power wire may be connected incorrectly and directs checking open phase and power supply voltages.

Stop useTechnician
Sourced Jul 2026
Applies to
Toshiba Carrier 26 High Wall
Homeowner fix
Turn the system off. Do not reset repeatedly, open panels, or move wiring.
When to call a pro
Call a licensed HVAC technician or qualified electrician for P05. Tell them Toshiba Carrier identifies P05 as open phase detected with power wiring and voltage checks.
View the fix ->

P07

The Toshiba Carrier table lists P07 as heat sink overheat. It says abnormal temperature was detected by the IGBT heat-sink temperature sensor.

Stop useTechnician
Sourced Jul 2026
Applies to
Toshiba Carrier 26 High Wall
Homeowner fix
Turn the system off if P07 returns. Keep debris away from the outside of the outdoor unit, but do not open the cabinet.
When to call a pro
Call a licensed HVAC technician if P07 returns. Tell them Toshiba Carrier identifies P07 as heat-sink overheat detected by the IGBT heat-sink sensor.
View the fix ->

P10

The Toshiba Carrier table lists P10 as indoor water overflow. It points to the drain pipe, clogged drainage, float switch circuit, and indoor PCB, and says drainage is out of order or the float switch activated.

Stop useTechnician
Sourced Jul 2026
Applies to
Toshiba Carrier 26 High Wall
Homeowner fix
Turn the unit off if water is visible. You may check only the outside end of the drain for an obvious blockage or kink; do not open the indoor unit.
When to call a pro
Call a licensed HVAC technician if P10 returns, water is leaking, or the drain is not easy to inspect from outside. Tell them Toshiba Carrier identifies P10 as indoor water overflow.
View the fix ->

P12

The Toshiba Carrier table lists P12 as abnormal operation of indoor fan. It points to an abnormal indoor fan motor, indoor PCB, and indoor DC fan conditions such as overcurrent or lock.

AdvisoryTechnician
Sourced Jul 2026
Applies to
Toshiba Carrier 26 High Wall
Homeowner fix
Turn the unit off if the indoor fan is not moving, is noisy, or smells hot. Check from outside that the inlet and outlet are not blocked.
When to call a pro
Call a licensed HVAC technician if P12 returns. Tell them Toshiba Carrier identifies P12 as abnormal indoor DC fan operation.
View the fix ->

P15

The Toshiba Carrier table lists P15 as gas leakage detected. It says there may be gas leakage from a pipe or connecting part and directs checking gas leakage.

Stop useTechnician
Sourced Jul 2026
Applies to
Toshiba Carrier 26 High Wall
Homeowner fix
Turn the system off, ventilate the area if you suspect a leak, and do not restart it. Do not tighten fittings or handle refrigerant lines.
When to call a pro
Call a licensed HVAC technician for P15. Tell them Toshiba Carrier identifies P15 as gas leakage detected from a pipe or connecting part.
View the fix ->

P19

The Toshiba Carrier table lists P19 as 4-way valve error. It points to the 4-way valve and indoor temperature sensors TC/TCJ, and says the error is due to temperature drop of the indoor heat exchanger during heating.

AdvisoryTechnician
Sourced Jul 2026
Applies to
Toshiba Carrier 26 High Wall
Homeowner fix
Power cycle once if you can do that safely. Do not open the outdoor unit or handle refrigerant components.
When to call a pro
Call a licensed HVAC technician if P19 returns or heating performance is poor. Tell them Toshiba Carrier identifies P19 as 4-way valve error during heating.
View the fix ->

P20

The Toshiba Carrier table lists P20 as high-pressure protective operation and identifies it as high-pressure protection.

Stop useTechnician
Sourced Jul 2026
Applies to
Toshiba Carrier 26 High Wall
Homeowner fix
Turn the system off. Make sure the outdoor unit is not blocked outside the cabinet, but do not open it or connect gauges.
When to call a pro
Call a licensed HVAC technician for P20. Tell them Toshiba Carrier identifies P20 as high-pressure protective operation.
View the fix ->

P22

The Toshiba Carrier table lists P22 as outdoor fan error. It points to the outdoor fan motor and outdoor PCB and says overcurrent or locking was detected in the outdoor fan drive circuit.

Stop useTechnician
Sourced Jul 2026
Applies to
Toshiba Carrier 26 High Wall
Homeowner fix
Turn the system off if the outdoor fan is not moving or is noisy. You may clear loose debris around the outside of the unit only if it is safe; do not reach into the fan.
When to call a pro
Call a licensed HVAC technician if P22 returns. Tell them Toshiba Carrier identifies P22 as outdoor fan overcurrent or locking.
View the fix ->

P26

The Toshiba Carrier table lists P26 as outdoor inverter Idc activated. It points to IGBT, outdoor PCB, inverter wiring, and compressor, and says short-circuit protection for compressor drive circuit devices was activated.

Stop useTechnician
Sourced Jul 2026
Applies to
Toshiba Carrier 26 High Wall
Homeowner fix
Turn the system off. Do not keep resetting it and do not open the outdoor unit.
When to call a pro
Call a licensed HVAC technician for P26. Tell them Toshiba Carrier identifies P26 as outdoor inverter Idc short-circuit protection.
View the fix ->

P29

The Toshiba Carrier table lists P29 as outdoor position error. It points to the outdoor PCB and high-pressure switch, and says a compressor motor position error was detected.

Stop useTechnician
Sourced Jul 2026
Applies to
Toshiba Carrier 26 High Wall
Homeowner fix
Turn the system off. Do not keep resetting it and do not open the outdoor unit.
When to call a pro
Call a licensed HVAC technician for P29. Tell them Toshiba Carrier identifies P29 as outdoor compressor motor position error.
View the fix ->

P31

The Toshiba Carrier table lists P31 as other indoor unit error. It says another indoor unit in the group is raising an alarm and points to E03, L07, L03, or L08 alarm locations.

AdvisoryTechnician
Sourced Jul 2026
Applies to
Toshiba Carrier 26 High Wall
Homeowner fix
Check whether another indoor unit or wired controller is also showing an alarm, then power cycle once if you can do that safely. Do not change group settings.
When to call a pro
Call a licensed HVAC technician if P31 returns. Tell them Toshiba Carrier identifies P31 as another indoor unit in the group raising an alarm.
View the fix ->