ACiQ ECC1 error code

ECC1 means the leak alarm came from a different indoor head on the same multi-zone system. Treat the whole system as unsafe until a technician verifies the leak sensor and refrigerant circuit.

Urgency
stop use
Verified
Jul 30, 2026
Fix path
Technician

What it means

ECC1 means the leak alarm came from a different indoor head on the same multi-zone system. Treat the whole system as unsafe until a technician verifies the leak sensor and refrigerant circuit.

Urgency

Likely causes

  1. Actual refrigerant leak at a flare joint, coil, line set, or service connection
  2. Low refrigerant charge or charge loss after installation or service
  3. Refrigerant sensor, T1/T2, or related control input reading abnormally
  4. Indoor or outdoor board fault only after the leak and sensor checks pass

Homeowner fix

Turn the system off, ventilate the space, avoid flames, sparks, and smoking, and do not reset the unit back into normal operation. Expected result: the system stays off until a licensed technician verifies the leak sensor and refrigerant circuit.

When to call a pro

Call a licensed HVAC technician immediately. Tell them the display is ECC1 and that another indoor unit's refrigerant sensor reported leakage.

This code points to refrigerant or sealed-system work - get repair quotes from contractors in your area.

Get repair quotes

Repair vs replace

A leak-sensor replacement or minor leak repair may be reasonable, especially under warranty. If the repair involves a coil, buried line set, or repeated refrigerant loss, compare the quote with replacement.

See ACiQ mini-splits

Your ACiQ model

Multi-Zone Extreme Series model pages in the ACiQ catalog help compare this repair path with current replacement options.

For your technician

Technician note: follow R-454B/A2L leak-safety procedures, identify the reporting indoor unit, verify sensor operation, locate and repair any leak before restart. Page context: ACiQ maps this display to the Multi-Zone Extreme Series line; source: ACiQ Multi-Zone Service Manual and shared Midea D5CMRA Table 20 display reference; display convention: match the letter E, letter C, letter C, and one marker exactly before comparing neighboring codes.

Which systems show it

  • ACiQ Multi-Zone Extreme Series R-454B systems using the shared Midea/ACiQ multi-zone platform.
  • ACiQ Multi-Zone Standard Series R-454B systems where the ACiQ service manual lists the same EC/EH/EL/PC diagnostics.
  • ACiQ wall-mounted, cassette, duct, console, and AHU indoor units listed in service manual section 7.2.

Sold under more than one brand

Shared with Midea. ACiQ and Midea document this code from the same manufacturer source, so ECC1 means the same thing on either badge and the steps above apply.

Open Midea ECC1

Related troubleshooting

Use the symptom guide alongside the exact display code if the unit is flashing, cycling, or showing comfort symptoms.

Reset note

Turn the system off, ventilate the space, avoid flames, sparks, and smoking, and do not reset the unit back into normal operation. Expected result: the system stays off until a licensed technician verifies the leak sensor and refrigerant circuit.

Manual trigger

ECC1 means the leak alarm came from a different indoor head on the same multi-zone system. Treat the whole system as unsafe until a technician verifies the leak sensor and refrigerant circuit.

Related codes

Source

ACiQ Multi-Zone Service Manual; Midea D5CMRA Installation Instructions
Section
Midea Table 20; Midea leak detection system warning; ACiQ service manual section 7.4.1.13
Page
Midea PDF page 37; Midea PDF pages 4-6; ACiQ PDF page 62; ACiQ PDF page 81

Short quote: "Other IDU refrigerant sensor detects leakage."

Sourced Jul 2026

Next step